Kitchen exhaust airflow calculator

Enter what you are cooking and how much of it, add the duct run, and get the airflow to specify plus the ESP filter model that covers it. Metric or imperial, m³/h or CFM.

  • Burner count or hood length
  • Duct length, 90° and 45° bends
  • System pressure and duct diameter
  • Model, dimensions and power

Short answer: a commercial kitchen exhaust needs roughly 2,000–3,000 m³/h per burner (about 1,200–1,800 CFM), or 2,000–2,500 m³/h per metre of hood face, multiplied by 1.25–1.5 for wok and grill work and then given a 20% margin. The purifier is chosen on that airflow; the fan is chosen on the total pressure the duct run creates. The calculator below does both and returns the KL-D-J model.

Units

Metric works in m³/h and metres; imperial in CFM and feet. Results show both either way.

What are you cooking?

This sets the multiplier on the base rate, from ×0.80 for steam to ×1.50 for solid fuel.

Size it by
stations

A wok range with six burners is six stations. A griddle counts as one per 600 mm of plate.

The duct run
m
90° bends
45° bends
Margin 20%

Each 90° bend counts as 6 m of straight duct, each 45° as 3 m. The margin covers a change of menu and a cell that is between washes.

How the arithmetic works

Three numbers decide an ESP filter

Airflow decides the cell size. Pressure decides the fan. Margin decides whether the two still work in eighteen months.

01

Airflow — from the cooking, not the room

Base rate 2,000–3,000 m³/h per burner, or 2,000–2,500 m³/h per metre of hood. Multiply by the cooking factor: 0.8 for steam, 1.0 for pan-fry, 1.25 for wok and fryer, 1.5 for charcoal. The room's floor area does not enter the sum.

02

Pressure — what the duct costs

Straight duct at about 1 Pa per metre, a 90° bend is worth roughly 6 m of straight pipe, a 45° about 3 m. Add the hood entry, the ESP cell (107–176 Pa clean) and the discharge. That total is what the fan has to overcome.

03

Margin — 20%, not 50%

20% covers a menu change, a filter between washes and the difference between a clean and a dirty cell. More than that and the fan runs off its curve: the duct gets noisy and the cell captures less, not more.

Reference rates used by the calculator

InputRateNotes
Per burner / station2,500 m³/hStandard wok or range burner; use 2,000 for light duty, 3,000 for high heat
Per metre of hood2,200 m³/hFace length of the canopy over the cooking, not the wall length
Steam / boil / holding× 0.80Steam is a moisture problem more than a grease problem
Pan-fry / griddle / stir-fry× 1.00The baseline the per-burner figure was written for
Wok range / deep fryer / chargrill× 1.25Add a water spray stage ahead of the cell on charcoal
Charcoal / tandoor / open flame× 1.50Sparks and ash — the water stage is not optional here
Straight duct1.0 Pa / mGalvanised duct at roughly 8 m/s
90° elbow≈ 6 m equivalentRadiused bends are less; tight square elbows are more
45° elbow≈ 3 m equivalentTwo 45s instead of one 90 is usually cheaper than more fan
ESP cell107–176 PaClean, by model; a dirty cell adds resistance
Design velocity8 m/sDuct sized to this keeps grease moving and noise down

Rates are the ones SOUNINY uses to quote KL-D-J models and are consistent with the selection guidance published for the series. Local codes may impose a different minimum for a given cooking type — where they do, the code governs.

Using the result

What to do with the numbers

The airflow figure is what you write on the specification and what the purifier is sized against. If it lands between two models, take the larger one: the difference in cabinet size is small, and an undersized cell is the single most common reason a kitchen fails an inspection six months after a perfectly good installation.

The pressure figure is the fan's problem, not the purifier's. A centrifugal fan rated at 10,000 m³/h free-air might deliver 7,000 m³/h against 400 Pa. That is why the calculator prints both numbers: the ESP model follows the volume, the fan follows the pressure, and if the fan cannot produce the volume, the purifier will never see the airflow it was chosen for.

Duct diameter at 8 m/s is a sanity check on the drawings. If the existing duct is much smaller than the figure shown, the velocity in it is higher than 8 m/s, the pressure loss is higher than this estimate, and the whole calculation moves in the wrong direction. Fixing the duct is usually cheaper than buying a bigger fan and a bigger purifier to compensate for it.

Where the cooking is charcoal or tandoor, add a water spray purifier in front of the ESP. The calculator sizes the electrostatic stage; the water stage is sized at the same airflow and protects the cell from the sparks and coarse ash that would otherwise shorten its life.

FAQ

Airflow questions, answered

How is kitchen exhaust airflow calculated?

Airflow is set by the cooking load and the geometry of the hood, not by the floor area of the room. The usual starting points are 2,000–3,000 m³/h per wok burner and 2,000–2,500 m³/h per metre of hood length, with a multiplier for high-heat work. A margin of 20% is then added so a change of menu does not mean replacing the unit.

Why does duct length and elbow count change the size?

Because they add resistance, not airflow. Every metre of straight duct, every 90° elbow, every 45° elbow and every diameter change adds pressure drop, and the fan can only move its rated volume against a certain total pressure. A long, bendy run either needs a bigger fan or a lower-resistance route — and the ESP cabinet has to be sized against the airflow the fan can actually deliver, not the figure on the fan label.

What does the duct allowance in this calculator actually do?

It converts the geometry of the run into an equivalent additional pressure loss and expresses it as a percentage uplift on the airflow you need to specify, so the purifier is not undersized when the duct is long or heavily bent. It is a selection aid, not a substitute for the fan curve: the final check is that the selected fan delivers the required volume at the total static pressure of the complete system.

Should I choose m³/h or CFM?

The calculator works in both. 1 m³/h equals 0.5886 CFM, so 10,000 m³/h is about 5,886 CFM. Our model numbers are quoted in m³/h — KL-D-J100 is 10,000 m³/h — and the result panel shows both so the figure can go straight onto a US or UK specification.

How much margin should I add?

20% over the calculated load is the normal allowance: it covers a change of menu, a filter that is between washes, and the difference between a clean and a dirty cell. Do not use margin to cover a bad duct route — fix the route instead, because every extra bend costs fan power for the life of the kitchen.

Is the calculated figure the final airflow?

It is the figure to specify. The final number is confirmed against the fan curve, the duct drawing and the appliance list — and where the site is tight, against the local code requirement for the cooking type. Send us the calculation and the layout and we will confirm the model on a drawing.

Next step

Send the layout. We will confirm the model.

Appliance list, hood length and the duct route are enough to come back with a model, an airflow figure and a drawing. OEM and ODM enquiries welcome.