One technology, seven kinds of kitchen

The cell does not change. What changes is how much air the cooking needs, what has to happen before the cell, and whether something has to happen after it. Those three answers are the whole specification.

  • Gas, induction and electric — cell alone
  • Charcoal and solid fuel — water first
  • Shared risers — one treatment point
  • Odour-sensitive sites — carbon last

If you only read one line. Airflow comes from the cooking, not the room: 2,000–3,000 m³/h per burner for wok and high-heat work, 2,000–2,500 m³/h per metre of hood for ordinary gas cooking. Charcoal, tandoor and solid-fuel grills take a water spray stage ahead of the cell; sites with neighbours, hotels or an odour condition take a carbon stage behind it.

The most common specification error on a commercial kitchen is sizing from floor area. A 200 m² restaurant with four burners and a tandoor needs less air than a 60 m² noodle bar with six woks, because the airflow requirement follows the heat and the grease load, not the rentable square metres. Once the airflow is right, the rest of the decision is about what the exhaust contains and who is downstream of it.

The table below is the working version of that logic: cooking type to airflow rate to the stage chain that experience says will pass inspection. Where a site sits between two rows, the higher rate applies.

Cooking type to stage chain

The table we work from

Rates are per unit of cooking, before the 20% margin. The chain reads left to right in the direction of airflow: hood, pre-stage, ESP cell, post-stage, fan, discharge.

Cooking type Design airflow Stage chain Typical model Wash interval
Wok / stir-fry, high heat2,500 – 3,000 m³/h per burnerHood → J → fan → dischargeKL-D-J200 – J4007 – 14 days
Gas range, oven, griddle2,000 – 2,500 m³/h per burnerHood → J → fan → dischargeKL-D-J80 – J16014 – 30 days
Induction / electric1,500 – 2,000 m³/h per stationHood → J → fan → dischargeKL-D-J40 – J10021 – 30 days
Charcoal, tandoor, solid fuel3,000 m³/h per burnerHood → SPL → J → fan → W → dischargeKL-D-SPL + KL-D-J + KL-D-WSPL continuously, cell 21 – 30 days
Combi ovens and steam1,000 – 1,500 m³/h per unitHood → J → fan → dischargeKL-D-J40 – J6030 days
Deep fryer line2,000 m³/h per vat batteryHood → J → fan → dischargeKL-D-J60 – J12014 – 21 days
Pizza / deck oven1,500 – 2,000 m³/h per deckHood → J → fan → dischargeKL-D-J60 – J10030 days
Food court, shared riserSum of tenants + 15% diversityTenant hoods → shared J or Q → fan → WKL-D-J320 – J640Q self-cleans; J 7 – 14 days
Coffee roaster1,000 – 3,000 m³/h per roasterCyclone → J → fan → WKL-D-J40 – J8014 – 21 days
Food processing, frying linePer line extraction volumeHood → J (or Q) → fan → WKL-D-J320 – J6407 – 14 days, or automated

Wash intervals assume a professional kitchen running two shifts. A single-shift site can move one band slower; a 24-hour operation moves one band faster. The self-cleaning KL-D-Q exists for sites where the interval will not be honoured.

Three that come up most often

Wok range, charcoal grill, shared riser

These three cover most of the enquiries that arrive with a photograph rather than a drawing.

Wok and stir-fry kitchens

The hardest ordinary case. A row of woks produces a plume of fine oil aerosol at high temperature, in bursts, and the kitchen is usually in a dense urban building with a short riser and neighbours above. Airflow is set per burner at the top of the range, and the margin matters: a wok line running flat out on a Friday night is not the same load as the same line at Tuesday lunch.

  • Per-burner sizing at 2,500–3,000 m³/h, plus 20% margin
  • Cell upstream of the fan, on the negative-pressure side, so no grease is pushed through a fan
  • Wash every 7–14 days; in practice this is where the KL-D-Q earns its price
  • Carbon stage only if there is an odour condition or a residential neighbour
Restaurant kitchen with a wok range and an electrostatic precipitator in the exhaust duct

Wok line, single riser, neighbours above — the case ESP filters were commercialised for.

Charcoal grill station producing heavy visible smoke

Solid fuel brings sparks, ash and radiant heat. The cell should never be the first thing they meet.

Charcoal, tandoor and solid-fuel grills

Solid fuel changes the problem rather than scaling it. The exhaust carries sparks that will puncture a cell, ash that will bridge the plates, and enough radiant heat to distort them. Putting an ESP directly on a charcoal hood is how cells fail in the first month.

The water spray stage ahead of the cell does three jobs at once: it quenches the sparks, drops the gas temperature, and washes out the coarse fraction so the cell only sees fine aerosol. What comes out of the stack afterwards is still smoky-smelling, which is where the carbon box belongs.

  • Water spray → ESP → carbon, in that order
  • Recirculating wash water via the KL-D-QT tank where mains supply is awkward
  • 90% odour removal from the W series on top of 95%+ particulate removal

Food courts and shared risers

Fifteen tenants, one riser, one landlord. Treating each kitchen separately means fifteen cabinets, fifteen wash rotas and fifteen things to fail inspection. Treating the shared riser means one large cabinet with one maintenance contract — and a diversity factor, because not every tenant peaks at once.

Sizing is the sum of the tenant airflows at roughly 85%, rounded up to the next model. Where the tenant mix includes a charcoal unit, its water stage stays at the tenant hood; the shared ESP handles what everyone has in common.

  • One treatment point on the riser, upstream of the common fan
  • Diversity factor 0.85 on the tenant sum, then 20% margin
  • KL-D-Q self-cleaning where the landlord, not the tenant, owns maintenance
Food court with several outlets sharing a central exhaust riser

A shared riser turns fifteen maintenance problems into one.

Beyond the restaurant

The same cell in less obvious places

Cooking effluent is the main market, not the only one. Anywhere a hot process puts oil aerosol into the air, the plate-type ESP is a candidate.

Compare the series
01

Hotels and banqueting

Large production kitchens with a low tolerance for smell in guest areas. The combination is a ducted ESP for the grease plus carbon for the odour, with the discharge routed away from air intakes and terraces. Continuous operation makes the self-cleaning cabinet worth its premium.

Typical: KL-D-Q + KL-D-W

02

Dark kitchens and central production

Twenty brands, one building, no front of house. Extraction runs long hours and nobody is on site to wash a cell, so the specification is driven by unattended reliability rather than purchase price. Automated washing plus a monitored drain is the whole design.

Typical: KL-D-Q + KL-D-QT

03

Food processing and frying lines

Continuous fryers, roasting tunnels and smokehouses produce a steady aerosol load rather than a bursty one. Airflow is set from the extraction volume of the line, and the wash interval is measured in shifts. Stainless construction and IP65 electrics matter more here than in a restaurant.

Typical: KL-D-J400 – J640, or KL-D-Q

04

Coffee roasting

Chaff, oily aerosol and a very persistent odour at comparatively low volume. A cyclone takes the chaff, the ESP takes the aerosol, and carbon takes the smell. Scaling a kitchen unit down does not work: the chaff load is the difference, and it has to leave the airstream before the cell.

Typical: cyclone + KL-D-J60 + KL-D-W

05

Industrial oil mist

Machining, quenching and metalworking produce a fine oil mist that is a health hazard rather than a nuisance. The same cell collects it; what changes is the ducting, the fire strategy and the fact that the collected oil is often worth recovering rather than draining away.

Typical: KL-D-J160 – J400

06

Markets, terraces and event pitches

No duct, no riser, no plant room, and a landlord who wants the smoke to stop before the neighbour complains. A water-cycle cart with treatment on board is the only arrangement that fits, which is why it exists as a product rather than as a modification.

Typical: KL-D-SMK cart, or Little Prince hood

What actually changes

Four dials, not four products

Between one application and the next, the cell is the same. What moves is airflow, what sits in front of the cell, what sits behind it, and how often it is washed.

 RestaurantCharcoal / solid fuelFood courtProcessing / coffee
Airflow driverBurner countFuel bed and hood faceSum of tenants, 0.85 diversityLine extraction volume
Pre-stageBaffle in the hoodWater spray, mandatoryTenant-level bafflesCyclone or knockout
CellKL-D-J or KL-D-QKL-D-J behind the SPLKL-D-J320 – J640, or QKL-D-J large frame, or Q
Post-stageCarbon only if requiredCarbon, almost alwaysCarbon on the shared riserCarbon for odour, UV if specified
Wash interval7 – 30 days21 – 30 days on the cell7 – 14 days, or automatedPer shift, or automated
Failure mode to design againstA cell nobody washedSparks reaching the cellOne tenant overloading the riserDowntime during production

Where a site combines two rows — a charcoal grill inside a food court, a roaster inside a production kitchen — the stricter pre-stage wins and the airflow is summed, not averaged.

Rooftop exhaust discharge from a commercial kitchen treatment system

Discharge position is part of the specification, not an afterthought. Treated air still has to leave somewhere sensible.

Compliance

The limit you are designing to is local — the design that meets it is not

Cooking-fume rules vary by country, by city and sometimes by the lease. Some jurisdictions set a mass concentration at the outlet, commonly in the region of 1–2 mg/m³. Others regulate visible emissions, which is a different test: a plume that is invisible in daylight generally passes where a measured value is not specified. Some require odour assessment at the nearest sensitive receptor.

What does not vary is what an ESP delivers. At 95–98% removal and 1–2 mg/m³ at the outlet, a correctly sized and correctly washed unit meets a mass-concentration limit on its own. Where the condition is odour at a receptor rather than mass at the stack, particulate removal alone will not satisfy it and a carbon stage is the answer.

  • Ask for the permit condition before choosing the chain, not after
  • Mass limits: ESP alone is normally sufficient
  • Opacity or visible-plume limits: ESP alone is normally sufficient, provided the cell is washed
  • Odour at a receptor: add carbon, and check the discharge height and direction

Questions we get before an order

Applications, answered plainly

Which cooking types need an ESP rather than a ductless hood?

Anything with a real grease load and an available duct: wok ranges, chargrills, fryers, tandoor ovens and busy restaurant kitchens. A ductless hood is for light to medium duty where no duct exists. The dividing line is the grease load, not the size of the room.

Can an ESP filter serve several kitchens on one riser?

Yes, and that is often the cheapest configuration: one treatment point on a shared exhaust instead of a unit per tenant. It needs the total volume calculated across all the stalls, a fan sized for the combined duty, and an access arrangement so each tenant's grease reaches the same sump. Food courts are commonly done this way.

What does a food processing plant need that a restaurant does not?

Continuous duty rather than service peaks, a higher tolerance for oil aerosol than for smoke, and a maintenance regime that fits a production shift. In practice that means larger cabinets, often stacked, and either a self-cleaning cell or a planned wash window. The filtration principle is the same.

Is an ESP suitable for a coffee roaster?

Roaster exhaust is a different problem: fine chaff, oily aerosol and a strong odour, at much lower volume than a kitchen. It needs a dedicated three-stage arrangement — pre-filter, washable cell, then HEPA and carbon — rather than a kitchen unit scaled down. Ask us for the roaster configuration if that is the application.

Next step

Send the layout. We will confirm the model.

Appliance list, hood length and the duct route are enough to come back with a model, an airflow figure and a drawing. OEM and ODM enquiries welcome.