Note · Technology
Electrostatic air purifiers compared: what the numbers mean
Sales sheets for electrostatic air purifiers converge on the same three claims: high efficiency, low running cost, no filters. The differences live in five numbers that are rarely on the same page.
Short answer. Compare clean-air delivery rate at the intended room volume, plate area, ozone output at rated airflow, pressure drop, and the wash interval at the actual particle load. Units that publish all five can be compared; units that publish a percentage cannot.
One: delivery, not efficiency
A 99% efficient unit moving 100 m³/h cleans less air than a 90% unit moving 600 m³/h. The product of the two is what changes a room, and it is the figure that domestic standards are built around. For commercial work, the equivalent question is whether the unit's airflow matches the duct or the room it serves.
Two: plate area
The physical measure of collection capacity. Two units at the same airflow with different plate area will diverge as soon as the load rises, because the smaller one saturates first. Ask in m².
Three: ozone
Every corona produces some. The number to ask for is mg/h at rated airflow, measured rather than modelled. It is the reason electrostatic units are not automatically the right choice for occupied rooms with vulnerable occupants.
Four: pressure drop
Determines the fan power and, in a ducted system, whether the fan you have will still deliver design airflow. Kitchen cabinets run 107–176 Pa clean; room units are lower because the fan is small and the airflow modest.
Five: wash interval
At your load, not at a test load. A unit rated for monthly cleaning in an office will need weekly cleaning in a kitchen, and a unit that assumes weekly cleaning in a site with no maintenance staff is a unit that will fail.
The comparison that actually matters
Media filters and electrostatic purifiers are not competing on the same axis: one trades consumables for certainty, the other trades attention for running cost. Where there are staff and a wash bay, the electrostatic unit is cheaper over its life. Where there are neither, it is a maintenance debt.
All the commercial units we build are plate-type with published plate area and pressure drop; the ESP filter table lists both per model so the comparison above can be made without a sales call.
What separates a kitchen ESP that lasts from one that does not is usually the wash regime, and that is a site decision, not a factory one.
Next step
Send the layout. We will confirm the model.
Appliance list, hood length and the duct route are enough to come back with a model, an airflow figure and a drawing. OEM and ODM enquiries welcome.