The electrostatic system: five parts, one performance figure
The cabinet is the part with the price on it, which is why it gets the attention. It is also the part least likely to be the limiting factor once the system is running.
Short answer. The system is capture, transport, filtration, motive power and control. A perfect cabinet behind an undersized hood with a fan sized on the clean filter will underperform from day one, and no adjustment inside the cabinet will change that.
Commissioning data from a badly balanced system looks like a filter fault: outlet concentration above expectation, a faint plume, a cell that draws less current than it should. The cell is fine. It is being fed the wrong air.
Capture
The hood sets the ceiling on everything. Canopy overhang, skirt depth, face velocity and the distance from the cooking surface decide what fraction of the plume enters the duct. A shortfall here is invisible at the cabinet and obvious in the room.
Transport
Duct velocity around 8 m/s keeps grease mobile without wasting fan pressure. Below about 6 m/s grease settles and the duct becomes a fire load; above 10 m/s pressure loss climbs faster than the benefit. Every 90° elbow costs roughly what 6 m of straight duct costs in pressure terms, which is why the layout matters as much as the length.
Filtration
The cabinet itself: 95–98% removal, 107–176 Pa clean pressure drop. The number to carry forward is not the clean figure but the loaded one, because that is the state the fan lives in for most of its life.
Motive power
The fan has to deliver design airflow against hood, duct, cabinet and discharge loss simultaneously — and it has to do it with a dirty cell. Fan curves are quoted at a reference density; hot exhaust and a roof terminal both move the operating point. The 20% margin in the airflow calculation is the simplest way to buy tolerance here.
Control
Interlocks, airflow proving, filter-differential alarms and, on larger systems, variable-speed demand control. A VSD that slows the fan when the kitchen is idle saves energy and quietly destroys capture, because hood face velocity falls with it. Set the minimum speed from the capture requirement, not from the motor rating.
What this means at quotation stage
Quotes that price only the cabinet are comparable with each other and not with reality. The useful comparison is total installed: hood, duct, cabinet, fan, controls, commissioning. Two quotes that differ by 15% on the cabinet can differ by 40% on the system, in either direction.
Every electrostatic precipitator we quote is priced from the same drawing — hood and fan included — because the failure modes that reach us are almost never inside the cabinet.
The engineering behind this is the same in every ESP filter we ship, from the 4,000 m³/h single cabinet to the 64,000 m³/h stack.
Next step
Send the layout. We will confirm the model.
Appliance list, hood length and the duct route are enough to come back with a model, an airflow figure and a drawing. OEM and ODM enquiries welcome.