Note · Technology
ESP efficiency: the five things that move the number
Efficiency figures are quoted as if they were a property of the machine, like weight. They are a property of the machine in a particular condition, and the condition is usually not the one on site.
Short answer. Plate cleanliness, actual airflow, velocity distribution, supply voltage and particle size distribution each shift ESP efficiency by several percentage points. The published 95–98% assumes a clean cell at design airflow with a properly distributed airstream.
One: plate cleanliness
The largest single variable in service. A cell at twice its design grease load loses a measurable share of its collection area to insulation, and the supply derates as leakage current rises. The two effects compound: less area, less voltage, less removal.
Two: actual airflow
Efficiency falls as airflow rises above design, because residence time falls with it. A system balanced at 20,000 m³/h that drifts to 26,000 m³/h because a damper was opened is a system running at 40% less dwell time than the specification assumed.
This is why the 20% design margin is applied to the cooking load and not used as spare capacity on the day.
Three: velocity profile
Air that runs down one side of the cabinet spends less time in the field, and air that bypasses the ioniser is never charged. A blocked pre-filter or a badly placed elbow upstream is enough to create both. It is invisible without a measurement, and it is the reason commissioning should include a traverse rather than a single reading.
Four: voltage and current
Higher field, better collection — up to the point where the cell arcs. A controller that has derated to 60% of nominal is telling you the cell is loaded or the insulators are tracking. Both are fixable, and both are usually ignored because nothing has actually failed.
Five: particle size
The 0.1–10 micrometre window is where the technology works best. Coarse droplets are removed by the pre-filter; the very finest fraction is removed least well. Change the menu from induction to charcoal and the inlet distribution changes with it.
How to know your real number
Measure outlet concentration once a year, in the same conditions, and compare. It costs an hour and it is the only figure that reflects the machine you own rather than the one in the brochure.
If the measurement shows a shortfall, the order of investigation is: wash interval, pre-filter, drain, electrical readings, airflow. The ESP filter data sheets give the clean pressure drop and design airflow to check the last of those against.
The engineering behind this is the same in every ESP filter we ship, from the 4,000 m³/h single cabinet to the 64,000 m³/h stack.