ESP filters 4,000–64,000 m³/h · CE certified · ISO 9001 · Shipping to 80+ countries

info@souniny.com / WhatsApp +86 189 2910 1713

Note · Kitchen

Kitchen exhaust filtration system: designing the whole line

A filtration system is a chain of resistances with a fan at one end. Design it as a chain and the numbers add up; design it as a filter with a fan attached and the airflow will be wrong at commissioning.

Short answer. Size the hood for capture, the duct for 8 m/s, the filter for the cooking load, the fan for the total of all three at the loaded condition, and the discharge for dispersion. Add 20% margin on airflow at the start.

The pressure budget is the artefact that holds the design together. Written out, it is five lines, and every one of them is checkable before anything is ordered.

The five lines

  • Hood entry: around 50 Pa for a canopy with filters.
  • Duct: roughly 1 Pa per metre at 8 m/s, plus 6 m equivalent per 90° elbow and 3 m per 45°.
  • Filtration: 107–176 Pa clean, higher loaded.
  • Discharge: 50 Pa for a stack terminal or weatherproof cowl.
  • Margin: the difference between a system that works in January and one that works on the day it was balanced.

Where it goes wrong

The duct is designed after the fan. The fan gets chosen on a rule of thumb, then the duct route changes and the resistance doubles. Fix the route first.

Velocity is chosen for noise rather than transport. Below about 6 m/s grease settles and the duct becomes a fire load. Quiet is achieved with silencers and a bigger duct, not with slow air.

The filter's loaded resistance is ignored. A cell at twice its clean pressure drop takes airflow away from the hood exactly when the kitchen is busiest.

Make-up air is an afterthought. A kitchen cannot extract air it cannot replace. Without make-up, the fan runs off its curve and the hood stops capturing, which reads as a filter fault and is not one.

The commissioning check

Measure airflow at the hood, not at the fan. Measure differential pressure across the cell and record the clean figure on the door. Both numbers, written down, are what turns a warranty conversation into a five-minute call.

Most of the systems we are asked to diagnose fail on lines one or five of the budget rather than inside the filter. The kitchen ESP cabinet is the middle line, and it is the only one that comes with a published pressure drop per model.

Everything described here is what gets built into a kitchen ESP before it leaves the factory — the cell, the drain, the interlock, the fan curve.

Next step

Send the layout. We will confirm the model.

Appliance list, hood length and the duct route are enough to come back with a model, an airflow figure and a drawing. OEM and ODM enquiries welcome.

Size it in 30 seconds Chat on WhatsApp