Note · Kitchen

Restaurant indoor air quality: the part the extract hood does not fix

A kitchen can have an excellent precipitator and terrible air, because the two are different problems solved by different parts of the same system. The extract takes air out; something has to bring air in, and it has to arrive in the right place.

Short answer. Indoor air quality in a restaurant depends on make-up air volume and distribution, pressure balance between kitchen and dining room, fine particulate in the breathing zone, and CO2 as a proxy for ventilation rate. The extract filter affects none of those directly.

The most common finding on a survey is a kitchen running at strong negative pressure. The extract is doing its job, the make-up air is undersized or badly placed, and the room compensates by pulling air through the dining area, the toilets and the back door.

Balance first

Extract and make-up should be within about 10% of each other, with the kitchen slightly negative relative to the dining room so cooking smells do not migrate. More negative than that and the doors pull, the hood stops capturing, and the gas appliances get less air than they need.

Where make-up air enters

Low level, away from the hood, and tempered in winter. Make-up air dumped directly under a canopy destroys capture by disturbing the plume — it looks like a filter problem and it is an air distribution problem.

What to measure

  • CO2 in the dining area: above about 1,000 ppm suggests the ventilation rate is short.
  • PM2.5 in the breathing zone during service, compared with outside. A ratio above about 2 during cooking is worth investigating.
  • Pressure difference kitchen to dining, measured with a simple manometer at the door.
  • Hood face velocity at several points, not one.

Where the extract filter fits

It protects the duct, the roof and the neighbours. It also keeps the fan clean, which keeps airflow at design, which keeps capture working — so it helps indoor air indirectly, and only if the rest of the system is balanced.

If the complaint is smoke in the room rather than smoke at the roof, the fix is capture and balance, not a bigger cell. Start with the hood, then check the make-up; the electrostatic precipitator stage is the last thing to change, not the first.

The electrostatic precipitator we would put on a job like this is the KL-D-J, in whichever size the airflow calculation returns.

Next step

Send the layout. We will confirm the model.

Appliance list, hood length and the duct route are enough to come back with a model, an airflow figure and a drawing. OEM and ODM enquiries welcome.