What do electrostatic precipitators do? Removal, not magic

The list of things a precipitator does is short. The list of things people expect it to do is long, and the gap is where complaints come from. Here is the honest split.

Short answer. It removes grease aerosol and fine smoke particles — typically 95–98% by mass — and with them most of the visible plume and most of the duct greasing. It does not remove odour molecules, water vapour, heat or carbon dioxide.

The distinction that clarifies everything: a precipitator acts on particles, and only on particles. Odour is a gas. Steam is a gas until it condenses. Heat is energy. None of those are particles, so none of them are collected, and a cabinet sold as solving all four is being oversold.

What goes

Grease aerosol. The main event. Droplets of rendered fat in the 0.1–10 micrometre range, which is exactly where the technology is strongest.

Fine smoke. Soot from chargrills and charcoal, and the sub-micron fraction that gives a plume its blue tint. Removal here is what turns a visible plume into a heat shimmer.

Most of the perceived smell. Not because odour molecules are captured, but because they travel adsorbed on the aerosol. Take the aerosol out and a good part of the smell goes with it — typically enough that the visible complaint stops, and not enough that a neighbour with a sensitive nose stops.

Duct fouling. The unglamorous benefit. A kitchen with a precipitator has a duct that stays close to its design pressure drop for years, which is a fire-risk reduction as much as a maintenance saving.

What stays

  • Odour in the gas phase — needs carbon, which is what the W series adds behind the cell.
  • Water vapour — visible as a plume in cold weather and often mistaken for smoke.
  • Heat — a cabinet does not cool the exhaust, and downstream components see the same temperature.
  • CO and CO2 — combustion products, unaffected.

The number that tells you it is working

Outlet concentration, in mg/m³, measured downstream of the cell. A working commercial unit holds 1–2 mg/m³. Read against the inlet — usually 5–30 mg/m³ depending on the cooking — that is the 95–98% figure, and it is the number a regulator will ask for.

Everything else on a data sheet is a proxy. Efficiency percentages without a test method are marketing; a visible plume is a lagging indicator that shows up weeks after the cell has started to fail.

If the requirement is “no visible plume and no grease on the roof”, a single-stage ESP filter in the right size will do it. If the requirement includes “no smell at the boundary”, the cell is the first half of the answer and a carbon stage is the second.

The dimensions, weights and pressure drops quoted here come from the ESP filter data sheets, not from a brochure rounded for print.